UF2000F Fix Mount Ultrasonic Water Flowmeter
UF2000F Fix Mount Ultrasonic Water Flowmeter
| Brand: | Sensor |
| Product Code: | Sensor |
| Availability: | 100 |
-
Rp0.0
- Ex Tax: Rp0.0
The Fix-mounting ultrasonic flow meter can be applied to a wide range of pipe flow measurements. Applicable liquids include pure liquids as well as liquid with small quantity of tiny particles.
Application
- Water (hot water, chilled water, city water, sea water, waste water, etc.);
- Chemicals (alcohol, acids, etc.);
- Plant effluent;
- Beverage, liquid food;
- Ultra-pure liquids;
Advantages
1. Linearity: 0.5%, Repeatability: 0.2%, Accuracy: ±1%.
2. Easy to operate.
3. Several type transducers for selection, measuring pipe size is from DN15mm to DN6000mm.
4. Adopt low voltage, multi-pulse technology to improve accuracy, useful life and reliability.
5. Powerful Recording Function, record the totalizer data of the last 64 days/64 months/5 years.
Technical Data
Spec | UF2000-F | ||
Host | Accuracy | Flow meter:±0.5%; heatmeter, ±1.0% | |
| Signal output | 1 channel 4~20mA currency output, impedance 0~1K, accuracy 0.1% | |
|
| 1 channel OCT pulse output (pulse width 6~1000ms, 200ms by default) | |
|
| 1 channel relay output | |
| Signal input | 3 channel 4~20mA currency input, accuracy 0.1%; temperature, pressure and liquid level signals can be collected. | |
|
| 3 wire PT100 can be connected to measure heat | |
| Data port | RS485, MODBUS etc. | |
Special cable | Generally less than 50m; for 485 communication, transmission distance can be more than 1000 meter. | ||
Pipe | Pipe material | Steel, S/S, iron steel, copper, PVC, aluminum, etc, liner allowed | |
| Pipe inner diameter | 15-6000mm | |
Medium | Type | Water, sea water, industrial sewage, acid and alkali solutions, alcohol, beer, various oils and other single uniform liquids that can conduct ultrasonic waves | |
| Temperature | -30~160℃ | |
| Turbidity | 10000ppm and the bubble content is small | |
| Flow rate | 0~±10m/s | |
Power consumption | 1.5W | ||
Power supply | DC8-36V or AC85-264V (Optional) | ||
Working temperature | Host: -20~60℃; Flow sensor: -30~160℃ | ||
Working humidity | Host & sensor can be immersed in water, water depth ≤ 2m (note:after wiring and potting) | ||
.png)